Your browser doesn't support javascript.
Show: 20 | 50 | 100
Results 1 - 1 de 1
Filter
Add filters

Database
Language
Document Type
Year range
1.
17th International Conference on Indoor Air Quality and Climate, INDOOR AIR 2022 ; 2022.
Article in English | Scopus | ID: covidwho-2324682

ABSTRACT

Risk assessment models typically assume ideal mixing, in which the pathogen-laden aerosol particles emitted by a person are evenly distributed in the room. This study points out the local deviation from this idealized assumption and a correlation between the level of pathogen concentration and the distance from the emitter. For this purpose, several numerical studies (CFD) were analyzed, and a validation experiment was performed. Statistical evaluation of the spatial pathogen distribution was used to determine the potential exposure to elevated pathogen concentrations. Compared to an ideally mixed room, at a distance of 1.5 m, the mixing ventilation cases show a 25% risk of being exposed to twice the amount of pathogens and a 5% risk to more than 5 times the assumed value. For displacement ventilation there is a 75% chance of being exposed to less pathogens than in complete mixing at a distance of 1 m. The measurement values agree with the simulation results. © 2022 17th International Conference on Indoor Air Quality and Climate, INDOOR AIR 2022. All rights reserved.